Carrier · Heat pump · Heating

Non-communicating heat pump: heating cycle (HK32EA001/007 and 003/008)

Performance

What happens, in order

  1. Thermostat makes R-Y and R-G on a call for heat (no R-O, so the reversing valve stays in heating position)
  2. R-Y feeds the safeties and energizes the contactor and terminal T1; T1 powers the defrost logic and defrost cannot work without it
  3. On 003/008 boards if compressor was off 5 min, OF2/T2 energize and outdoor fan and compressor start
  4. On 001/007 boards the contactor and fan start straight away; there is no compressor delay on these boards
  5. Thermostat satisfied R-Y drops and compressor and fan stop; 003/008 boards restart the 5-minute timer

Timings and thresholds

ItemValue
Compressor time delay5 min (003/008 only)

Applies to: Carrier / Bryant / Payne split heat pumps with HK32EA defrost control boards (Performance Series and Comfort Series)

Models

HK32EA001HK32EA007HK32EA003HK32EA008

More Carrier heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier-Bryant residential A/C + HP Application Guideline and Service Manual (R-410A, 24-25), System Function and Sequence of Operation, Defrost Control. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.