Carrier · Heat pump

84 High pressure lockout (4 hours)

High severity Carrier Infinity 18VS 25VNA8Carrier 2-stage 24ANB/25HNBCarrier single-stage communicating HP

What the control is telling you

Amber STATUS light flashes 84. The high pressure switch kept opening and the unit could not stage down any further (elevated from code 31). 4-hour lockout. Type: System malfunction; reset: 4 hours.

Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8 (AOC control + inverter)

Likely causes

  • Cooling: Outdoor airflow too low or off / dirty or iced coil
  • Cooling: Overcharged system or indoor TXV problem
  • Cooling: EXV restriction with a long line set causing overcharge when charged in cooling
  • Cooling: Restriction in circuits or tubing
  • Heating: Indoor airflow too low or off / dirty filter or coil
  • Heating: Furnace running together with the heat pump (dual fuel)
  • Heating: Overcharged system
  • Heating: Reversing valve stuck in cooling
  • Service valve left closed
  • Loose HPS harness or HPS unplugged from the inverter
  • Restricted filter drier
  • Non-condensables in the system
  • Faulty pressure switch

Test and repair steps

  1. Check and clean the outdoor coil and fan (cooling) and the indoor filter, coil and blower (heating).
  2. Cooling check subcooling in Charging Mode (or the subcooling chart on the control box door) and adjust charge.
  3. Heating overcharge recover, evacuate and weigh in, then recheck by subcooling in cooling when conditions allow.
  4. Dual fuel if the furnace runs at the same time as the heat pump outside defrost, troubleshoot the furnace / thermostat.
  5. Troubleshoot the reversing valve.
  6. Make sure both service valves are open.
  7. Check the HPS harness, pins and its connection to the inverter.
  8. Check for a temperature drop across the filter drier.
  9. Non-condensables recover, replace the drier, evacuate and recharge.
  10. If discharge pressure on a gauge is below about 600 psig (±20) while the switch reads open, replace the pressure switch.
  11. Troubleshoot the TXV and EXV.

Models that show this code

15 models in Carrier Infinity 18VS 25VNA8, Carrier 2-stage 24ANB/25HNB, Carrier single-stage communicating HP

25HNB62425HNB63625HNB64825HNB66025HNB92425HNB93625HNB94825HNB96025VNA81325VNA82425VNA82525VNA83625VNA83725VNA84825VNA860

Other codes on the same units

  • 79 Compressor / inverter fault (failed start)
  • 81 Low stage thermal lockout
  • 82 Suction over temperature lockout
  • 83 Low pressure lockout (4 hours)
  • 86 Fan inverter current lockout
  • 88 Compressor / inverter lockout
  • 91 Inverter DC over voltage (event)
  • 92 Inverter DC under voltage (event)

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.24. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.