Navien · Water heater troubleshooting

Wire push button switches to the HotButton controller

NPN/NHW700

What is going on

Wired push buttons need no power source. Several switches can go in parallel on the same terminals, or on a common branch circuit.

Check in this order

  1. Run each switch cable to the controller terminals, or run a common branch from the controller and tie each switch to the branch.
  2. Use spade connectors at cable ends for secure terminal connections.
  3. Use UTP cable or cable larger than AWG 24.
  4. Keep total cable length at or under 100 m (328 ft).
  5. Connect no more than 10 push button switches to one controller.
  6. Use Navien part #GXXX001426 for extra push buttons and #GXXX001427 for wall plates.

Applies to: HotButton Kit push button wiring

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien HotButton add-on controller installation manual, p. 2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.