Navien · Water heater troubleshooting
Venting a closet or small enclosure
What is going on
Enclosures under 640 ft³ need air exchange so the heat pump does not chill the room and lose efficiency. Acceptable options depend on the enclosure size.
Likely causes
- Enclosure smaller than 640 ft³ with no air exchange.
- Room temperature drops to where the heat pump cannot run efficiently.
Check in this order
- For enclosures of 640 ft³ or more, no added ventilation is listed.
- For 84 to 639 ft³, use a fully louvered door, or one wall grille at least 12 in from the ceiling plus a second grille at least 12 in from the floor.
- Make each wall grille at least 22 in by 6 in, or give it at least 130 in² of net free airflow.
- Under 84 ft³, the unit should not be placed in that space.
Applies to: NWP500 series, closets and small enclosures
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NWP500 installation manual, p. 19-21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.