Navien · Water heater troubleshooting

Venting a closet or small enclosure

NWP500

What is going on

Enclosures under 640 ft³ need air exchange so the heat pump does not chill the room and lose efficiency. Acceptable options depend on the enclosure size.

Likely causes

  • Enclosure smaller than 640 ft³ with no air exchange.
  • Room temperature drops to where the heat pump cannot run efficiently.

Check in this order

  1. For enclosures of 640 ft³ or more, no added ventilation is listed.
  2. For 84 to 639 ft³, use a fully louvered door, or one wall grille at least 12 in from the ceiling plus a second grille at least 12 in from the floor.
  3. Make each wall grille at least 22 in by 6 in, or give it at least 130 in² of net free airflow.
  4. Under 84 ft³, the unit should not be placed in that space.

Applies to: NWP500 series, closets and small enclosures

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NWP500 installation manual, p. 19-21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.