Top installation of the recirculation pump

ComfortCirc

What is going on

Mounting the recirculation pump on the top of the water heater, including routing the communication cable through the top plate and removing the RE-PUMP cable from the controller.

Check in this order

  1. Make sure electrical power to the water heater is off.
  2. Pick a recirculation loop and pump location using the standard piping diagrams.
  3. Cut a slit in the rubber packing so the pump communication cable can pass through.
  4. Remove the rubber packing and fit it at the designated point.
  5. Seat the rubber packing properly in the top plate hole.
  6. Remove the 2 screws at the bottom of the front panel and take the panel off the water heater.
  7. Disconnect the RE-PUMP cable from the controller.

Applies to: NAP-10SS ComfortCirc pump, top-mounted installation

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien ComfortCirc installation and operation manual, p. 14-16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.