Navien · Water heater troubleshooting

T&P valve leaking

NWP500

What is going on

Water leaks from the T&P relief valve. The manual gives these corrective measures.

Likely causes

  • Excess pressure on the cold water side
  • Thermal expansion in a closed system

Check in this order

  1. Install a pressure reducing valve (PRV) on the cold water inlet, set to about 50–60 psi.
  2. Install an expansion tank rated for the system pressure.
  3. Adjust the tank temperature setting as needed.

Applies to: NWP500-50, NWP500-65, NWP500-80

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NWP500 installation manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.