Side installation of the recirculation pump kit
What is going on
Connects the recirculation pump through the lower heating element cover. Power must be off before starting.
Check in this order
- Turn off electrical power to the water heater.
- Pick a location for the recirculation loop and pump using the standard piping diagrams.
- Remove the two screws from the lower heating element cover and take the cover off.
- Connect the pump's communication cable to the RE-PUMP cable from the water heater, then power the pump with the supplied power adapter.
- Keep all cables secured inside the element cover.
- Route the cable through the opening in the lower heating element cover and refit the cover.
- Check all piping connections for leaks before switching the water heater on.
Applies to: ComfortCirc recirculation pump, side-mount installation
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien ComfortCirc installation and operation manual, p. 18-19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.