Navien · Water heater troubleshooting
Routing and pitching the condensate drain
What is going on
The condensate line must flow freely to an adequate drain. Excessive run length or bends restrict flow.
Likely causes
- Long runs or excessive bends.
- Outlet submerged in the discharge area.
- Condensate line combined with another drain line.
Check in this order
- Use 3/4 in NPT female thread at the condensate drain.
- Pitch the line downward at least 1/4 in per 1 ft.
- Keep the run short and avoid bends so water flows freely.
- Keep the outlet out of standing discharge water.
- Insulate the line if needed to prevent external condensation.
- If no drain is nearby, install a condensate pump rated no less than 2 GPD and route it to an alternate drain, following the pump maker's instructions.
- Run the condensate line separately from other drain or discharge lines.
Applies to: NWP500 series
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NWP500 installation manual, p. 22-23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.