Navien · Water heater troubleshooting

Replace the heating element

NWP500

What is going on

High-voltage work. Power must be off, and the tank must be full before restart.

Check in this order

  1. Turn off power to the water heater.
  2. Drain and flush the tank (section 6.4).
  3. Remove the 2 screws on the upper and lower heating element covers and take the covers off.
  4. Pull the safety cover forward to remove it.
  5. Remove the 2 screws holding the element wires and disconnect them.
  6. Turn the element counterclockwise with a socket wrench and remove it.
  7. Install the new element and connect the 2 wires with 2 screws.
  8. Reinstall the safety cover and element covers.
  9. Fill the tank, check the element for leaks, then turn the unit on and confirm normal operation.

Applies to: NWP500-50, NWP500-65, NWP500-80

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NWP500 installation manual, p. 66. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.