Limiting high incoming water pressure

NWP500

What is going on

Pressure above the recommended range can damage the tank and cause early leaks. Some homes run above 100 psi.

Likely causes

  • Incoming water pressure too high, up to 100 psi or more.
  • No pressure reducing valve on the main cold line.

Check in this order

  1. Measure line pressure with a gauge on the cold line, watching the peak and current readings through the day.
  2. Install a pressure reducing valve on the main incoming cold line.
  3. Set the valve between 50 and 60 psi.
  4. Choose a PRV that has a built-in bypass.

Applies to: NWP500 series

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NWP500 installation manual, p. 17-18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.