Installing the leak detection system (optional accessory)
What is going on
Sensor detects water in its location and alerts through an error code on the front panel, flashing light and audible signal. Alert can also be seen in the NaviLink app. If a shut-off valve is fitted, it closes automatically on a leak.
Check in this order
- Make sure power to the water heater is off.
- Remove the two screws from the lower heating element cover and take the cover off.
- Connect the leak detection system to the extension cable.
- Connect the other end of the extension cable to the LEAK cable inside the cover.
- Route the cable through the opening in the lower heating element cover, then reinstall the cover.
- Attach the leak sensor to the side of the water heater or to the floor or drain pan with double-sided tape, about 0.2 in (5 mm) above the floor or pan.
- For top installation, reconnect the controller and install the front panel with the two bottom screws.
Applies to: NWP500-50, NWP500-65, NWP500-80
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NWP500 installation manual, p. 32-33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.