Navien · Water heater troubleshooting
Heat pump operation prevention (display shows Operation Prevention in Progress)
What is going on
The heat pump only runs when the ambient air is between 41°F (5°C) and 113°F (45°C) and the tank water is between 50°F (10°C) and 149°F (65°C). Outside these ranges the heat pump stays off and the front panel shows Operation Prevention in Progress.
Likely causes
- Ambient air temperature outside 41°F to 113°F
- Tank water temperature outside 50°F to 149°F
Check in this order
- Check the ambient temperature around the unit.
- Check the tank water temperature.
- Wait for conditions to return to the operating range; no action is needed if they are within range soon.
Applies to: NWP500 series
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NWP500 installation manual, p. 61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.