Navien · Water heater troubleshooting

Ground wiring with metal conduit

NWP500

What is going on

Conduit can be used as the ground path if it meets the limits below. For full grounding detail, follow the current NFPA-70 edition.

Check in this order

  1. Use a 10 AWG solid copper grounding conductor, continuous with no splices or joints, when conduit is not used as the ground.
  2. Rigid metal conduit, intermediate metal conduit or EMT can be used if terminated in grounding-approved fittings.
  3. Flexible metal conduit or tubing can be used only if the ground return path is 6 feet (1.8 m) or less.
  4. For flexible conduit, the circuit must be protected by a 30 A overcurrent device.
  5. Terminate flexible conduit or tubing in grounding-approved fittings.

Applies to: NWP500-50, NWP500-65, NWP500-80

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NWP500 installation manual, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.