Navien · Water heater troubleshooting

External pump installation guidelines

H2Air

What is going on

General guidelines for an external circulator pump on H2Air systems.

Check in this order

  1. Size the circulation at 2 to 4 GPM.
  2. Wire pumps rated 150W, 1.5A or lower to the water heater PCB using the Navien External Pump Wire (GXXX001319).
  3. Connect the pump to the water heater PCB directly with the Navien External Pump Cable (GXXX001319).
  4. Check the installation manual for the specific water heater model for further pump wiring guidelines.
  5. Install an anti-scalding device and set the DHW output to 115-120 °F.
  6. Use a spring check valve on vertical pipe runs. Do not use a swing check valve on vertical piping.
  7. Use a spring check valve or a swing check valve on horizontal runs.
  8. Use 18 AWG wire for thermostat installation.
  9. Install only certified mixing valves and expansion tanks.

Applies to: External pump installations with H2Air

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien H2Air installation manual, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.