Navien · Water heater troubleshooting
Delayed hot water at fixture with recirculation on
What is going on
Hot water arrives late at the fixture when recirculation is enabled.
Likely causes
- Recirculation pump off temperature set too low
- Recirculation pump runs too short
- No water flowing in the recirculation piping
Check in this order
- Adjust the recirculation Off Diff. Temp setting or raise the tank set temperature (see page 54).
- Adjust the Recirculation Interval Time to lengthen pump run time (see page 54).
- Run the Recirculation Pump Test to check flow and confirm circulation.
- If there is no flow, check for a clogged pump, strainer blockage, or air trapped in the piping.
Applies to: NWP500-50, NWP500-65, NWP500-80
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NWP500 installation manual, p. 72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.