Navien · Water heater troubleshooting

Delayed hot water at fixture with recirculation mode on

NWP500

What is going on

Hot water takes too long to reach the fixture when recirculation is enabled.

Likely causes

  • Recirculation pump OFF temperature set too low
  • Recirculation pump run time too short
  • No water flowing in the recirculation piping

Check in this order

  1. Adjust the recirculation Off Diff. Temp setting (see p. 54) or raise the tank set temperature.
  2. Adjust the Recirculation Interval Time (see p. 54) to extend pump run time.
  3. Run the Recirculation Pump Test to check flow rate and confirm water is circulating.
  4. If there is no flow, inspect for a clogged pump, strainer blockage, or trapped air in the piping.

Applies to: NWP500-50, NWP500-65, NWP500-80

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NWP500 installation manual, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.