Navien · Water heater troubleshooting
Connecting the T&P relief valve discharge pipe
What is going on
The T&P relief valve is factory installed. Its discharge pipe must be sized, sloped and routed so pressure can always be relieved. Never reuse an old T&P valve and never put a valve or restriction on it.
Check in this order
- Do not reuse an old T&P relief valve.
- Confirm the T&P valve pressure rating does not exceed 150 psi.
- Do not connect any valve or restriction to the T&P relief valve.
- Use a discharge pipe of at least ¾ inch diameter, sloped for drainage.
- Use pipe rated for 250°F (121°C) that will not kink.
- End the discharge pipe within 6 inches (15 cm) of the floor.
- Keep all piping free from freezing and clear of blockages between the heater and the valve.
- Connect the discharge per local code.
Applies to: NWP500-50, NWP500-65, NWP500-80
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NWP500 installation manual, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.