Connecting the T&P relief valve discharge pipe

NWP500

What is going on

The T&P relief valve is factory installed. Its discharge pipe must be sized, sloped and routed so pressure can always be relieved. Never reuse an old T&P valve and never put a valve or restriction on it.

Check in this order

  1. Do not reuse an old T&P relief valve.
  2. Confirm the T&P valve pressure rating does not exceed 150 psi.
  3. Do not connect any valve or restriction to the T&P relief valve.
  4. Use a discharge pipe of at least ¾ inch diameter, sloped for drainage.
  5. Use pipe rated for 250°F (121°C) that will not kink.
  6. End the discharge pipe within 6 inches (15 cm) of the floor.
  7. Keep all piping free from freezing and clear of blockages between the heater and the valve.
  8. Connect the discharge per local code.

Applies to: NWP500-50, NWP500-65, NWP500-80

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NWP500 installation manual, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.