Navien · Water heater troubleshooting

Condensate drain clogged or overflow

NWP500

What is going on

Condensate system needs no routine care. Compressor stops automatically when leakage or overflow is detected.

Likely causes

  • Sediment buildup in the condensate drain pan or hose.
  • Algae buildup in the condensate drain pan or hose.
  • Condensate leakage or overflow detected by the unit.

Check in this order

  1. Turn off electrical power to the water heater.
  2. Remove the condensate drain and open the cleaning port.
  3. Clear debris with a brush or pipe cleaner through the cleaning port.
  4. Use a vacuum or bleach if needed to remove remaining debris.
  5. Reinstall the cleaning port and restore power.

Applies to: NWP500 series

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NWP500 User's Information Manual, p. 28. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.