Navien · Water heater troubleshooting
Condensate drain clogged or overflow
What is going on
Condensate system needs no routine care. Compressor stops automatically when leakage or overflow is detected.
Likely causes
- Sediment buildup in the condensate drain pan or hose.
- Algae buildup in the condensate drain pan or hose.
- Condensate leakage or overflow detected by the unit.
Check in this order
- Turn off electrical power to the water heater.
- Remove the condensate drain and open the cleaning port.
- Clear debris with a brush or pipe cleaner through the cleaning port.
- Use a vacuum or bleach if needed to remove remaining debris.
- Reinstall the cleaning port and restore power.
Applies to: NWP500 series
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NWP500 User's Information Manual, p. 28. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.