Weak or missing flame signal (flame rod checks)
What is going on
Low flame signal on a Rinnai is nearly always the rod itself or its connection. Flame rod, ground and board all have to agree before the unit stays lit, and a rod that is dirty or loose will drop the flame after a few seconds. Get a reading before you replace parts. Gas appliance, so shut off and be careful opening up the burner area. Do the checks the way the Electrical Diagnostics page lays them out.
Likely causes
- Carbon or damage on the flame rod, which insulates the tip from the flame
- Loose or damaged flame rod wiring or a poor connector at the rod or board
- Old flame rod gasket reused, letting combustion products or air leak at the mounting
- Poor ground path through the burner assembly or a weak board input
Check in this order
- Run the heater and measure AC volts between the flame rod and ground. A healthy rod reads roughly 5 to 150 VAC, so a reading outside that range sends you to the wiring or board.
- Put the meter on the microamp range in series with the rod. 1 microamp or more is a good flame circuit, and anything below that explains the faults you are chasing.
- Shut the unit down and let it cool. Unplug it before working near the rod and its wiring.
- If the signal is low, remove the rod and inspect it for carbon or damage. Clean light carbon, replace the rod if it is pitted or bent.
- Check the rod lead and connector for corrosion, heat damage or a loose fit.
- Always fit a new flame rod gasket after the rod has been removed, never the old one.
- Retest the microamp reading after reassembly and confirm a stable flame before closing up.
- Gas leak check any joint you disturbed, and call a licensed tech if you are unsure.
Applies to: SENSEI RX/CX (RX199i, RX180i, RX160i, RX130i, CX199i, CX160i, RXP199i, RXP160i, CXP199i, CXP160i)
More tankless water heater guides
- BMS Gateway: building system cannot talk to the gateway
- BMS Gateway: cannot log in to the setup screens
- BMS Gateway: gateway cannot see the tankless heaters
- BMS Gateway: reset IP address and admin password to default
- Checking PC board fuses and thermistors
- CO sensor / combustion air fault (code number not printed on these pages)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai SENSEI RX/CX technical guide U362-0875, Electrical Diagnostics. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.