Rinnai · Tankless water heater troubleshooting

BMS Gateway: reset IP address and admin password to default

Rinnai BMS Gateway

What is going on

Puts the gateway back to IP 192.168.1.151, subnet 255.255.255.0, default gateway 192.168.1.254, admin password admin.

Likely causes

  • Forgotten password or IP

Check in this order

  1. Turn off power before opening the enclosure or unplugging connectors. The reset is done with the cover off, so work carefully around the board.
  2. Take off the six plastic screws and remove the front cover.
  3. Find the router inside the enclosure.
  4. Press and hold its IP Reset button. When the LED stops blinking and goes off, let go.
  5. Power cycle the gateway.
  6. Refit the cover.
  7. Touch screen passcode (separate from the web login) is 0151 by default, set on the Screens Setup tab.

Applies to: Rinnai BMS Gateway with up to 6 commercial condensing tankless units (SENSEI CU160/CU199, CX160/CX199 or KB C199; do not mix KB and SENSEI on one gateway)

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai BMS Gateway Installation and Operation Manual (R-BMS-100 / RBMS100E / R-BMS-101, 2025), 10.2 Reset IP Address and Password to Default p.54; 7.2 p.43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.