Rinnai · Tankless water heater troubleshooting

CO sensor voltage check (PCB connector C1)

Non-SENSEI

What is going on

Voltage check on the CO sensor of a non-SENSEI Rinnai tankless, at the PC board. A meter reading tells you whether the sensor and its wiring look healthy.

Likely causes

  • CO sensor failed or drifting out of range
  • Bad connection at connector C1

Check in this order

  1. Measure at connector C1, between the red and black wires, pins 1 to 5, using DC volts.
  2. Normal reading is 1.9 to 2.1 VDC.
  3. During combustion, expect 2.5 to 3 VDC.
  4. Check the connector C1 for a loose pin or corrosion if readings are off.
  5. If readings are out of range, follow the CO sensor steps before replacing parts.
  6. Combustion and CO issues on a tankless are not a DIY repair, so use a licensed technician.

Applies to: Units with CO sensor

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Troubleshooting Tankless Water Heater Diagnostic Codes, p. 37. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.