Rinnai · Tankless water heater troubleshooting

Hot water still flowing with the unit off (bleed-down or cross-over)

Non-SENSEISENSEI

What is going on

Water keeps flowing at fixtures after the hot supply is shut off. The cause is a faulty fixture, check valve, cross-over, or mixing valve.

Likely causes

  • Faulty fixture diaphragm
  • Faulty check valve in the plumbing or circulation return
  • Cross-over in the plumbing
  • Faulty mixing valve

Check in this order

  1. Ask the customer to describe the problem.
  2. Turn off the hot water ball valve on the Rinnai valve kit at the unit. Open a hot fixture and wait about two minutes for residual water to drain.
  3. If water still flows at any rate, find and repair the faulty fixture, check valve or cross-over.
  4. If there is a circulation loop, close the loop's shut-off valve in the return line. If flow stops, the loop is clear.
  5. At each single-handle fixture, close the cold ball valve one at a time and watch flow. If flow stops, reopen the last valve closed. If flow restarts, that fixture has a bad diaphragm; replace the insert or add a hot-line check valve.
  6. If the location has a mixing valve, isolate it and shut off its cold feed. If the water stays at temperature, the mixing valve is the problem.

Applies to: SENSEI and Non-SENSEI series

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Troubleshooting Tankless Water Heater Diagnostic Codes, p. 62. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.