Rinnai · Tankless water heater troubleshooting
Rack system: units not sharing load / controller shows ---
What is going on
Heaters on a TRS/TRW/TRX rack are linked with cascade cables (up to 24 units) so they take turns and modulate as one. A secondary that shows --- has no ID yet.
Likely causes
- Cascade cable missing or plugged into the wrong port
- Cascade jumper missing on an open port
- No unit set as Primary
- Secondary IDs not set
- Different models mixed on one cascade
Check in this order
- Power off before plugging cables.
- Each cable goes from Cascade OUT on one PCB to Cascade IN on the next. Fit the cascade jumpers (come with the cable) on the open end ports.
- Do not mix different models on one cascade.
- On the unit you want as Primary, set parameter 08 to Primary. Its controller shows the system set temp. Others stay Secondary (factory default).
- Set the Secondary IDs on each secondary press On/Off. The display changes from --- to its ID number.
- On the Primary, parameter 09 sets how many units sit in standby with their water valve open. The rest keep the valve closed until needed.
- TRW03CXP link the three units with cascade cables. TRW02CXP: link the two CXP199 units with an EZConnect cable.
Applies to: Rinnai TRS/TRW/TRX tankless rack systems with SENSEI CX / CXP heaters
More tankless water heater guides
- BMS Gateway: building system cannot talk to the gateway
- BMS Gateway: cannot log in to the setup screens
- BMS Gateway: gateway cannot see the tankless heaters
- BMS Gateway: reset IP address and admin password to default
- Checking PC board fuses and thermistors
- CO sensor / combustion air fault (code number not printed on these pages)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai TRS with SENSEI CX Installation Instructions (100000870), 12 Connect Water Heaters p.37-38; 11 p.32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.