Rinnai · Tankless water heater troubleshooting

CXP rack (TRW02CXP / TRW03CXP): recirculation set-up and slow hot water

SENSEI RX/CX

What is going on

CXP199 units have a built-in pump (Smart-Circ). The rack needs either a dedicated return line or a thermal bypass valve at the far fixture, and the parameters must match.

Likely causes

  • Parameter 04 not matching the piping
  • Loop too long
  • MC-195T-US and Control-R Wi-Fi module both installed
  • Used with hydronic heating

Check in this order

  1. Dedicated return line set parameter 04 to dedicated mode (04b). No return line: fit a thermal bypass valve at the far fixture and set 04C (crossover).
  2. Loop limit 400 ft with 3/4 in. pipe or 100 ft with 1/2 in. pipe, counting elbows.
  3. Parameter 05 sets pump cycling 05A Economy (default), 05b Comfort (runs more), 05C Commercial (runs on and off all the time, more wear).
  4. Do not install the MC-195T-US timer and the Control-R Wi-Fi module together.
  5. Do not use these racks with hydronic heating.
  6. Insulate the hot and return lines.

Applies to: Rinnai TRW02CXP and TRW03CXP racks (CXP199)

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai TRS with SENSEI CX Installation Instructions (100000870), 11 Configuring TRW02CXP and TRW03CXP Rack Models p.31-36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.