Viessmann · Mini-split troubleshooting
Zero crossing detection error
What is going on
The control checks the zero crossing signal interval. The correct interval is 6 to 13 ms. If the interval is wrong for 240 seconds continuously, the unit stops and the LED shows the failure (EH 02).
Likely causes
- Zero crossing signal interval outside 6 to 13 ms for 240 s
Check in this order
- Check the zero crossing signal timing on the indoor board.
- Check power supply quality at the indoor unit.
Applies to: Indoor unit power input
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSHC service manual, p. 10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.