Viessmann · Mini-split troubleshooting

Check supply voltage on single-zone system before start-up

DLFSHC

What is going on

Measure voltages at the outdoor disconnect, outdoor terminal block, and indoor unit, then record on the checklist.

Check in this order

  1. Turn off the main disconnect and lock it out before opening any panels.
  2. At the outdoor disconnect, measure 1(L1) to GND, 2(L2) to GND, and 1(L1) to 2(L2).
  3. At the outdoor terminal block, repeat the same three measurements.
  4. At the indoor unit, measure 1(L1) to GND, 2(L2) to GND, 1(L1) to 2(L2), and 2(L2) to 3(S).
  5. Record the readings on the start-up checklist.

Applies to: Single zone system

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSHC installation instructions, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.