Wire the signal and power cable to the indoor unit
What is going on
The field 14/3 cable feeds power and communication from the outdoor unit to the indoor unit.
Check in this order
- Size the wires per NEC or CEC and local code, using the MCA and MOCP values on the outdoor unit rating plate or instructions.
- Run 14/3 power and communication cable two AC power wires, one communication wire and one ground wire. Do not use BX cable.
- Keep polarity correct between the indoor and outdoor units.
- In high EMF areas with communication problems, a 14/2 stranded shielded cable can replace wires 2 and 3, with the shield grounded at the outdoor unit only.
- Open the front cover, remove the lower panel and open the wire cover. Unscrew and set aside the cable clamp below the terminal block.
- Remove the plastic panel on the lower left at the back of the unit and feed the signal wire through from back to front.
- Connect each wire to its matching terminal using a u-lug, and screw it firmly.
- Fasten the cable with the clamp, then replace the wire cover and the back panel.
- Do not mix up live and ground wires.
Applies to: DLFSHC indoor units
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSHC installation instructions, p. 13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.