Wire the signal and power cable to the indoor unit

DLFSHC

What is going on

The field 14/3 cable feeds power and communication from the outdoor unit to the indoor unit.

Check in this order

  1. Size the wires per NEC or CEC and local code, using the MCA and MOCP values on the outdoor unit rating plate or instructions.
  2. Run 14/3 power and communication cable two AC power wires, one communication wire and one ground wire. Do not use BX cable.
  3. Keep polarity correct between the indoor and outdoor units.
  4. In high EMF areas with communication problems, a 14/2 stranded shielded cable can replace wires 2 and 3, with the shield grounded at the outdoor unit only.
  5. Open the front cover, remove the lower panel and open the wire cover. Unscrew and set aside the cable clamp below the terminal block.
  6. Remove the plastic panel on the lower left at the back of the unit and feed the signal wire through from back to front.
  7. Connect each wire to its matching terminal using a u-lug, and screw it firmly.
  8. Fasten the cable with the clamp, then replace the wire cover and the back panel.
  9. Do not mix up live and ground wires.

Applies to: DLFSHC indoor units

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSHC installation instructions, p. 13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.