Temporarily bypass the 24V interface to set static pressure

DLFSDAHDLFLDAHVitocal IND-D

What is going on

With a 24V interface installed, the wireless remote, wired controllers and Wi-Fi kit are disabled. The interface must be bypassed to use the wired controller for static pressure setup, then restored.

Check in this order

  1. Turn off power to the unit.
  2. Unplug CN11 (to outdoor) and CN12 (to indoor) on the 24V interface.
  3. Sizes 9K to 24K add a jumper from the indoor S terminal to the outdoor S terminal.
  4. Sizes 36K to 58K disconnect S1 and S2 at the 24V interface (CN8, CN9) and splice outdoor S1 to indoor S1 and outdoor S2 to indoor S2.
  5. Connect the wired controller KSACN0701AAA and complete the static pressure setup.
  6. Disconnect the wired controller.
  7. Sizes 9K to 24K remove the S jumper from the terminal block.
  8. Sizes 36K to 58K remove the splice and reconnect S1 and S2 to the 24V interface.
  9. Plug CN11 and CN12 back in, then restore power.

Applies to: Ducted indoor units with 24V interface KSAIC**

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann DLFSDAH & DLFLDAH Technical Data Manual, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.