Set static pressure or automatic airflow with the wired controller

DLFSDAHDLFLDAHVitocal IND-D

What is going on

Use the wired controller (KSACN0701AAA) to pick a fan curve SP1 to SP4 or run automatic airflow (AF) for the duct system. Confirm the coil is dry first.

Check in this order

  1. Run the unit 2 hours in FAN ONLY mode to dry the coil if it is wet.
  2. Check the power wiring and ducting are complete, dampers are set, and the filter is in place.
  3. If there is more than one inlet or outlet, balance the dampers so each matches design airflow. Run FAN ONLY and use AF to step airflow from H to L.
  4. Turn the indoor unit OFF with the wired controller.
  5. With the system off, press and hold COPY for about 4 seconds.
  6. Press + or - to scroll to SP or AF. Do not select the T1, T2, T2b, T3 or T4 thermistor sub-menus.
  7. For manual SP select SP, press CONFIRM, pick SP1 to SP4, then power down the unit to lock the setting.
  8. For AF select AF and press CONFIRM. The ON light flashes during the run. Wait 3 to 6 minutes for the run to finish and the unit to stop.

Applies to: Ducted indoor units, wired controller KSACN0701AAA

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann DLFSDAH & DLFLDAH Technical Data Manual, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.