Viessmann · Mini-split troubleshooting

Set external static pressure or run automatic airflow adjustment

DLFSDAH and DLFLDAH

What is going on

Setting the fan performance to match the ducts, using the wired controller.

Check in this order

  1. Confirm the test run is on a dry coil; if not, run FAN ONLY for 2 hours to dry it.
  2. Check power wiring and duct work are finished, any closing dampers are open, and the filter is fitted in the return.
  3. Adjust dampers so each inlet and outlet matches its design airflow, with the unit in FAN ONLY.
  4. Use the airflow button on the remote to choose H or L, then turn the indoor unit OFF.
  5. With the system off, press and hold COPY for about 4 seconds.
  6. Press + or - to scroll to SP or AF, then press CONFIRM.
  7. For manual SP pick SP1 to SP4 using the fan curves, then power down the unit to lock it in.
  8. For AF press CONFIRM. ON flashes while the fan runs; the unit stops by itself after 3 to 6 minutes.
  9. If there is no charge to the ventilation paths after adjustment, reset the automatic airflow adjustment and contact the dealer if it persists.

Applies to: Ducted indoor units with wired controller KSACN0501AAA

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal IND-D technical data manual, p. 13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.