Viessmann · Mini-split troubleshooting
Remove the stepper motor
What is going on
Remove the panel first. Open the louver and release the hooks to reach the motor cover.
Check in this order
- Remove the panel.
- Open the louver and push the hooks in the directions shown in the manual.
- Remove the 2 screws holding the motor cover and take off the cover.
- Remove the 2 screws and lift out the stepper motor.
Applies to: DLFSOAH indoor units 09XAK and 18XAK
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSOAH Service Manual, p. 53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.