Remove the fan motor and fan
What is going on
Remove the panel, electrical parts, water collector, water pump and evaporator first. The fan motor and fan come out as one assembly, and the motor can then be separated.
Check in this order
- Remove the panel, electrical parts, water collector, water pump and evaporator.
- Remove the 2 screws of the fan motor base.
- Pull out the fan motor and fan assembly.
- Remove the screw and separate the fan motor from the fan.
Applies to: DLFSOAH indoor units 09XAK and 18XAK
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSOAH Service Manual, p. 52. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.