Viessmann · Mini-split troubleshooting
Remove the fan and fan motor
What is going on
The evaporator subassembly must be removed first. The unit has two motor covers.
Check in this order
- Remove the evaporator subassembly.
- Remove the 1 screw and 1 hook, then take off the motor cover (there are two).
- Pull the fan motor and fan assembly out from the side.
- Remove the screw and take out the fan motor.
Applies to: DLFSFBH indoor floor console unit, 12K
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal IND-F DLFSFBH service manual, p. 47. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.