Viessmann · Mini-split troubleshooting
Remove the evaporator and coil temperature sensor T2
What is going on
Remove the panel, water collector and water pump first. T2 is the coil temperature sensor. Its ribbon must be cut and the ground screw removed.
Check in this order
- Remove the panel, water collector and water pump.
- Remove the 2 screws of the pipe clamp board.
- Remove the 2 screws on the left side of the evaporator bracket.
- Remove the 2 screws on the right side of the evaporator.
- Cut the ribbon, pull out coil temperature sensor T2 and remove the 1 ground screw.
- Remove the evaporator.
Applies to: DLFSOAH indoor units 09XAK and 18XAK
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSOAH Service Manual, p. 50-51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.