Viessmann · Mini-split troubleshooting

Remove main control board or electronic control box

Vitocal IND-ODLFSOAH

What is going on

Electrical parts removal. Remove the panel first. Anti-static gloves must be worn. Choose between repairing the main control board assembly (steps 1 to 4) or the electrical control box subassembly (steps 5 and 6).

Check in this order

  1. Open the left cover of the panel.
  2. Remove 2 screws and take off the electronic control box cover.
  3. Remove 2 screws from the air switch cover.
  4. Disconnect the connectors, then remove the main control board (3 clips).
  5. To repair the electrical control box subassembly, remove the 4 screws of the subassembly.
  6. Remove the electronic control box subassembly.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSOAH Service Manual, p. 44-47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.