Remove filter and front panel from one way cassette indoor unit

Vitocal IND-ODLFSOAH

What is going on

Front panel and filter removal on the DLFSOAH indoor unit. Panel removal differs depending on whether the panel has a lift function.

Check in this order

  1. If the panel has a lift function, grab the air grille and pull it out slowly.
  2. If the panel has no lift function, push in one side of the grille clamp on both sides, then remove 2 screws.
  3. Turn the air inlet grille assembly over and remove the filter.
  4. Open the two covers on both sides of the panel and remove 3 screws.
  5. Open the louver and the screw cover, then remove the screw.
  6. Remove 3 more screws.
  7. Separate the panel from the water collector and remove the panel.
  8. Remove 2 screws and take off the electronic control box cover.
  9. Disconnect the display board connectors and the stepper motor, then release the panel.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSOAH Service Manual, p. 39-42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.