Refrigerant pipe buried in the ground

VITOCAL IND-F

What is going on

Buried refrigerant pipe has length and rise limits. Too much buried pipe lets refrigerant migrate into the cold buried section during shutdown, which can cause liquid slugging and damage the compressor at start-up.

Likely causes

  • Refrigerant migrating to a cold buried section during long shutdowns
  • Liquid slugging at compressor start-up

Check in this order

  1. Do not bury more than 36 in (914 mm) of refrigerant pipe.
  2. If any section is buried, give it a 6 in (152 mm) vertical rise to the outdoor unit valve connections.

Applies to: All sizes, field-installed refrigerant piping

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal IND-F DLFSFA/DLFLFA installation manual, p. 3. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.