Viessmann · Mini-split troubleshooting

Refrigerant line set-up and charge

Vitocal 100-S

What is going on

Rules for installing the line set between the outdoor and indoor unit.

Check in this order

  1. Use the factory R410A charge. Line sizing and capacity are based on runs up to 25 ft (7.6 m).
  2. For runs longer than 25 ft, add 0.69 oz per ft (65 g per m) of extra refrigerant charge.
  3. Do not bury lines deeper than 36 in (914 mm).
  4. Give the service valves a vertical rise of at least 6 in (152 mm) to stop refrigerant migration.
  5. Insulate the suction line with at least 3/8 in (10 mm) wall thermal insulation.
  6. Isolate the tubing from the building structure so vibration and noise do not carry into the structure.
  7. Flow nitrogen while brazing the line set or line set adapters.

Applies to: DLCURA outdoor units with ductless indoor unit

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCURA technical data manual, p. 82. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.