Refrigerant line set-up and charge
What is going on
Rules for installing the line set between the outdoor and indoor unit.
Check in this order
- Use the factory R410A charge. Line sizing and capacity are based on runs up to 25 ft (7.6 m).
- For runs longer than 25 ft, add 0.69 oz per ft (65 g per m) of extra refrigerant charge.
- Do not bury lines deeper than 36 in (914 mm).
- Give the service valves a vertical rise of at least 6 in (152 mm) to stop refrigerant migration.
- Insulate the suction line with at least 3/8 in (10 mm) wall thermal insulation.
- Isolate the tubing from the building structure so vibration and noise do not carry into the structure.
- Flow nitrogen while brazing the line set or line set adapters.
Applies to: DLCURA outdoor units with ductless indoor unit
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCURA technical data manual, p. 82. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.