Viessmann · Mini-split troubleshooting

Refrigerant line installation

Vitocal IND-C

What is going on

Lines are shipped with R410A charge on the outdoor unit. Buried lines need limits and a rise at the service valves.

Check in this order

  1. Do not bury lines in the ground.
  2. If a line must be buried, keep the buried length to 36 in (914 mm) or less.
  3. Provide at least a 6 in (152 mm) vertical rise to the service valves to stop refrigerant migration.
  4. Insulate both lines with at least 1/2 in (12.7 mm) thick insulation.
  5. Use closed-cell insulation for long line runs.
  6. Isolate interconnecting tubing from the building structure so vibration and noise do not transfer.

Applies to: All 24K, 36K, 48K systems

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocal IND-C ductless technical data manual, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.