Viessmann · Mini-split troubleshooting
Refrigerant line installation
What is going on
Lines are shipped with R410A charge on the outdoor unit. Buried lines need limits and a rise at the service valves.
Check in this order
- Do not bury lines in the ground.
- If a line must be buried, keep the buried length to 36 in (914 mm) or less.
- Provide at least a 6 in (152 mm) vertical rise to the service valves to stop refrigerant migration.
- Insulate both lines with at least 1/2 in (12.7 mm) thick insulation.
- Use closed-cell insulation for long line runs.
- Isolate interconnecting tubing from the building structure so vibration and noise do not transfer.
Applies to: All 24K, 36K, 48K systems
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocal IND-C ductless technical data manual, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.