What is going on

Verify supply and protection before making any field electrical connections.

Check in this order

  1. Turn off the main power and lock out and tag the disconnect before any wiring work.
  2. Check that supply voltage is within 90-110% of the rated voltage.
  3. Use an approved circuit breaker or switch that disconnects all poles, with at least 1/8 in (3 mm) contact separation.
  4. Connect the unit to its own individual branch circuit, with no other appliance on that circuit.
  5. Properly ground the unit.
  6. Make sure every wire is tight. Keep wires away from refrigerant tubing, the compressor and moving parts.
  7. Wait at least 10 minutes after power is off before touching electrical components.
  8. Follow the wiring diagram on the indoor unit front panel and the electrical connection diagram on the indoor and outdoor panels.

Applies to: DLFSHC indoor and outdoor units

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSHC installation instructions, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.