Viessmann · Mini-split troubleshooting
Power and communication wiring, sizes 36 to 58
What is going on
Power runs from the outdoor unit to the indoor unit on three conductors: two high-voltage AC and one ground, factory recommended 14/2 stranded with ground. Communication needs its own separate shielded stranded copper conductor rated 600 V, double insulated.
Check in this order
- Size all wires per NEC or CEC and local code, using the electrical data MCA and MOCP values.
- Run 14/2 stranded power wire with ground from the outdoor unit to the indoor unit.
- Run a separate shielded 16 GA stranded control wire for communication, rated 600 V with double insulation.
- Tighten every connection and keep wires away from refrigerant tubing, the compressor and moving parts.
- Make sure a disconnect is within sight of and readily accessible from the unit.
Applies to: DLFLFAH36XAK, DLFLFAH48XAK, DLFLFAH58XAK
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal IND-F DLFSFA/DLFLFA installation manual, p. 4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.