Viessmann · Mini-split troubleshooting

Power and communication wiring, sizes 36 to 58

VITOCAL IND-F

What is going on

Power runs from the outdoor unit to the indoor unit on three conductors: two high-voltage AC and one ground, factory recommended 14/2 stranded with ground. Communication needs its own separate shielded stranded copper conductor rated 600 V, double insulated.

Check in this order

  1. Size all wires per NEC or CEC and local code, using the electrical data MCA and MOCP values.
  2. Run 14/2 stranded power wire with ground from the outdoor unit to the indoor unit.
  3. Run a separate shielded 16 GA stranded control wire for communication, rated 600 V with double insulation.
  4. Tighten every connection and keep wires away from refrigerant tubing, the compressor and moving parts.
  5. Make sure a disconnect is within sight of and readily accessible from the unit.

Applies to: DLFLFAH36XAK, DLFLFAH48XAK, DLFLFAH58XAK

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal IND-F DLFSFA/DLFLFA installation manual, p. 4. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.