Power and communication wiring, sizes 12 to 24
What is going on
Power is fed to the outdoor unit and runs to the indoor unit on a field-supplied 14/3 cable. Two conductors are high-voltage AC, one is communication, and one is ground. Use the shielded 14/2 option only in high EMF areas where communication problems occur.
Check in this order
- Size all wires per NEC or CEC and local code, using the electrical data MCA and MOCP values.
- Run a 14/3 power and communication cable from the outdoor unit to the indoor unit.
- If communication faults occur in a high EMF area, replace L2 and S with 14/2 stranded shielded wire.
- Land the shield on ground at the outdoor unit only.
- Tighten every connection and keep wires away from refrigerant tubing, the compressor and moving parts.
- Make sure a disconnect is within sight of and readily accessible from the unit.
Applies to: DLFSFAH12XAK, DLFSFAH18XAK, DLFSFAH24XAK
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal IND-F DLFSFA/DLFLFA installation manual, p. 4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.