Viessmann · Mini-split troubleshooting

Power and communication wiring, sizes 12 to 24

VITOCAL IND-F

What is going on

Power is fed to the outdoor unit and runs to the indoor unit on a field-supplied 14/3 cable. Two conductors are high-voltage AC, one is communication, and one is ground. Use the shielded 14/2 option only in high EMF areas where communication problems occur.

Check in this order

  1. Size all wires per NEC or CEC and local code, using the electrical data MCA and MOCP values.
  2. Run a 14/3 power and communication cable from the outdoor unit to the indoor unit.
  3. If communication faults occur in a high EMF area, replace L2 and S with 14/2 stranded shielded wire.
  4. Land the shield on ground at the outdoor unit only.
  5. Tighten every connection and keep wires away from refrigerant tubing, the compressor and moving parts.
  6. Make sure a disconnect is within sight of and readily accessible from the unit.

Applies to: DLFSFAH12XAK, DLFSFAH18XAK, DLFSFAH24XAK

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal IND-F DLFSFA/DLFLFA installation manual, p. 4. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.