Viessmann · Mini-split troubleshooting

Multi-zone: one room heats, another will not cool - DLC multi-zone

Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoorViessmann DLFSHB high wall indoor

What is going on

Viessmann Vitocal 200-S multi-zone (DLCM(R/H)B outdoor with DLFSHB high wall heads): one room heats, another will not cool. Normal behaviour, not a failure.

Likely causes

  • Mode conflict between indoor units, since one outdoor unit cannot heat and cool at once

Check in this order

  1. Heating has priority, because the outdoor unit follows heat when modes clash. If unit A is cooling or on fan and unit B is set to heat, A shuts off and B heats.
  2. If A is heating and B is set to cool or fan, B goes to standby because the outdoor unit is already committed to heat, and A keeps heating.
  3. Set all running indoor units to the same mode (fan with cool is fine), because mixed modes are the only conflict.
  4. Tell the customer so they know it is how the system works

Applies to: DLCM(R/H)B multi-zone outdoor units with DLFSHBH high wall indoor units (Midea, Carrier, Viessmann)

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Indoor units mode conflict p.44. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.