Viessmann · Mini-split troubleshooting

Mounting sizes 18K to 58K (floor console or underceiling)

Vitocal IND-F

What is going on

These sizes can be floor mounted or installed underceiling using hanging screw bolts.

Check in this order

  1. Install four 3/8 in. (Ø10) hanging screw bolts at the spacing shown in the manual's figures 15 and 16.
  2. Confirm the ceiling construction with on-site construction staff. The mounting location must be flat.
  3. Remove the side boards and grille.
  4. Locate the hanging arm on each hanging screw bolt and install the unit.
  5. If a roof beam must be cut, strengthen and consolidate the beam to prevent vibration.

Applies to: Sizes 18K to 58K

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSFA and DLFLFA installation instructions, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.