Viessmann · Mini-split troubleshooting

Maintain indoor unit clearances

DLFSHC

What is going on

Keep the required space around the indoor unit so return airflow and service access are not restricted.

Check in this order

  1. Keep at least 5.9 in (15 cm) above the unit for return airflow.
  2. If space is tight, the top clearance can be reduced to 2 in (50 mm), but only if the left and right clearances are still met.
  3. Keep at least 4.75 in (12 cm) clearance on the sides.
  4. Reducing the top clearance may reduce unit performance.
  5. Check the 6 ft (1.8 m) dimension shown in the clearance figure against the job layout.

Applies to: All DLFSHC indoor units

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSHC installation instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.