Main control board removal (36K High Heat, 48K Standard and High Heat, 60K Standard and High Heat)
What is going on
Removes the main control board and the fan motor capacitors. Note the wiring to the IPM module board, the T3/T4 sensors, the low and high pressure switches and the indoor unit connection (TP).
Check in this order
- Remove two screws to disconnect the power supply wires.
- Remove three screws to disconnect the ground wires.
- Disconnect the wires connected to the main control board.
- Disconnect the wires between the main control board and the IPM module board.
- Remove the four screws, release the six hooks and remove the main control board.
- Remove one screw per fan motor capacitor and remove the capacitors.
Applies to: Models 36K High Heat, 48K Standard and High Heat, 60K Standard and High Heat
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCURA service manual, p. 70 of 84. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.