Viessmann · Mini-split troubleshooting

Install wired wall remote controller (801 kit)

DLFSHC

What is going on

Wire the 801 kit harness and multi-function board between the main board and display board.

Check in this order

  1. Access the main board and display board inside the indoor unit.
  2. Remove the existing 7-pin to 4-pin harness between the main board and display board.
  3. Fit the 801 kit harness 4-pin to the main board, 7-pin to the display board, and 3-pin to the multi-function board.
  4. Mount the multi-function board in the reserved area beside the display.
  5. Connect the 3-pin harness to the CN40 input on the multi-function board.
  6. Cut the female end of the connection cable and wire the terminal block: X brown, Y yellow, E ground (black, white or copper), 5 VDC red.
  7. Refer to the controller's installation manual for setup.

Applies to: Wired controller

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSHC installation instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.