Viessmann · Mini-split troubleshooting

Install interconnecting piping and wiring to the indoor unit

DLFSHC

What is going on

Run the lines from the outdoor unit to the indoor unit, hang the indoor unit, then make the flare connections.

Check in this order

  1. Run the interconnecting piping and wiring from the outdoor unit through the wall hole to the indoor unit.
  2. Lift the indoor unit onto the mounting plate, hook the upper claw, then push the lower part up until it is fully hooked.
  3. Open the front cover, remove the field terminal block cover, and connect the outdoor wiring per the connection diagram.
  4. Replace the terminal cover and close the front cover.
  5. Cut the pipe square at 90 degrees with a pipe cutter and remove all burrs without letting any fall inside the tube.
  6. Remove the service connection if fitted, then fit the correct flare nut to the tubing.
  7. Oil the flare seat lightly, align the pipe centre with the valve, and tighten the flare nut to the torque in the torque table.

Applies to: Indoor unit installation

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSHC installation instructions, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.