Viessmann · Mini-split troubleshooting

Indoor fan speed too low

Vitocal IND-O

What is going on

Indoor fan speed protection. Fan speed can drop below the minimum for a set time.

Likely causes

  • Indoor fan speed remains below 300 RPM

Check in this order

  1. Expect the indoor fan to shut off after 50 seconds at low speed and restart 30 seconds later.
  2. If the protection trips three times while the fan keeps restarting, the unit stops and the LED shows the failure.
  3. Check the indoor fan motor, its wiring and the control board, then restart the unit.

Applies to: Indoor fan motor and control

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSOAH Service Manual, p. 7-8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.