Viessmann · Mini-split troubleshooting

Indoor fan speed out of control

Vitocal IND-F

What is going on

The indoor fan speed stays too low. The unit shuts the fan off and retries. After three failed restarts the unit stops and the LED shows the failure.

Likely causes

  • Fan speed stays below 300 RPM for 50 seconds

Check in this order

  1. Check the indoor fan motor and its wiring.
  2. Check that the fan runs freely and is not blocked.
  3. Confirm the fan is getting correct supply and control signals.
  4. After the fault clears, watch that the fan holds speed during operation.

Applies to: Indoor fan, DLFSFBH 12K

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.